Validation Error

Refrigerant Superheat & Subcooling Calculator

Diagnose refrigerant charge, metering device operation, and system performance using suction/liquid pressure and temperature readings. Supports all common HFC and HCFC refrigerants with built-in pressure–temperature charts.

Superheat Subcooling Charge Diagnosis
Superheat
Suction side — compressor protection & charge
Subcooling
Liquid side — condenser & charge verification

Superheat Inputs

Suction side readings
Please select a refrigerant type.
Read from low-side gauge at service valve
Enter a suction pressure between 0 and 800 psig.
Clamp thermometer on suction line at service valve, insulate probe
Enter a suction temperature between -60 and 200 °F.

What is Superheat?

Superheat is the temperature difference between the actual temperature of the refrigerant vapor and its boiling point (saturation temperature) at the same pressure. A positive superheat value confirms that all liquid refrigerant has fully boiled to vapor before reaching the compressor.

Superheat = Suction Line Temp − Saturation Temp (at suction pressure)

Compressors are designed to compress vapor, not liquid. Even a small amount of liquid refrigerant entering the compressor causes slugging, which can bend connecting rods and destroy valve reeds. Adequate superheat is the primary safeguard.

What is Subcooling?

Subcooling is the temperature difference between the condensing (saturation) temperature at the condenser pressure and the actual liquid line temperature. A positive subcooling value confirms that all refrigerant vapor has fully condensed to liquid before reaching the metering device.

Subcooling = Saturation Temp (at liquid pressure) − Liquid Line Temp

Without adequate subcooling, refrigerant can flash to vapor in the liquid line or at the inlet of the metering device, reducing capacity and causing erratic TXV operation. Subcooling also provides a buffer for pressure drop in the liquid line piping.

Normal Ranges

Superheat target ranges:

  • TXV / EXV systems: 8–14°F at the evaporator outlet (valve controls to its own setpoint, typically 10°F)
  • Fixed-orifice / piston systems: 15–25°F measured at the service valve (varies with outdoor temp and load)
  • Always check the equipment manufacturer’s specifications — some TXV systems target as low as 6°F

Subcooling target ranges:

  • Typical systems: 8–14°F at the liquid service valve
  • Systems with long liquid line runs: target the higher end (12–16°F) to compensate for line pressure drop
  • Manufacturer spec sheets often list target subcooling; use them when available

Diagnostic Guide

Low Superheat (<5°F):

  • Possible refrigerant overcharge
  • TXV stuck open or set too low
  • Restricted airflow across evaporator (dirty coil, blower issue)
  • Oversized metering device

High Superheat (>20°F):

  • Possible refrigerant undercharge (most common cause)
  • TXV stuck closed or hunting
  • Restricted liquid line, filter-drier, or metering device
  • Low evaporator airflow starving the coil

Low Subcooling (<5°F):

  • Possible refrigerant undercharge
  • Condenser fan issue (dirty coil, low RPM, failed motor)
  • Excessive ambient temperature at condenser

High Subcooling (>20°F):

  • Possible refrigerant overcharge
  • Restricted metering device (low superheat accompanies this)
  • TXV bulb not making contact with suction line

Zeotropic Refrigerants & Temperature Glide

Pure refrigerants and azeotropes (like R-410A) boil and condense at a single, constant temperature at a given pressure. Zeotropic blends (like R-407C) behave differently: they have a temperature glide, meaning the vapor and liquid phases exist at different temperatures at the same pressure.

For zeotropic refrigerants, two saturation temperatures are defined:

  • Dew point — the temperature at which the last drop of liquid vaporizes (used for superheat)
  • Bubble point — the temperature at which the first bubble of vapor forms (used for subcooling)

This calculator automatically uses the dew point for R-407C superheat calculations and the bubble point for subcooling calculations, matching industry-standard practice.

Safety Reminders

  • Always wear safety glasses when working with refrigerant gauges
  • Use calibrated manifold gauges appropriate for the refrigerant pressure range
  • Never mix different refrigerants — always identify the refrigerant type before connecting gauges
  • Recover refrigerant before opening any system — venting is illegal under EPA Section 608
  • R-410A operates at nearly twice the pressure of R-22 — use high-pressure rated equipment
  • Let the system run for at least 10–15 minutes under normal load before taking readings
Every field below is optional. The more you enter, the more the calculator can tell you about the system. Fill in what you have — skip what you don't.
Affects target superheat and charging method. TXV is most common in modern equipment.
Outdoor dry-bulb temperature at the condenser
Temperature of air entering the evaporator (return duct)
Temperature of air leaving the evaporator (supply duct)
Indoor wet-bulb temp (for target superheat on fixed-orifice systems)
Total airflow across the evaporator coil
Rated cooling capacity from the equipment nameplate
Measured static pressure drop across the air filter
Measured static pressure drop across the evaporator coil

Electrical Measurements (for efficiency analysis)

Enter voltage and amps at minimum. Power factor defaults to 0.85 if not known. Phase defaults to single-phase.
Measured supply voltage at the disconnect or contactor
Total system amps (compressor + condenser fan) from clamp meter
From power analyzer if available. 0.80-0.90 typical for A/C compressors.
Single phase for most residential; three phase for commercial

Enter your gauge pressure and line temperature readings, then click Calculate to see results and charge diagnosis.

Common Refrigerant Quick Reference

Properties, applications, and oil types for common HVAC/R refrigerants
Refrigerant Type ODP GWP Typical Application Replaces Oil Type
R-410A HFC Blend (Azeotrope) 0 2,088 Residential & light commercial A/C, heat pumps R-22 (retrofit not possible) POE
R-22 HCFC 0.055 1,810 Legacy residential A/C, heat pumps Mineral / Alkylbenzene
R-134a HFC (Pure) 0 1,430 Automotive A/C, refrigeration, chillers R-12 PAG (automotive) / POE
R-404A HFC Blend (Near-Azeotrope) 0 3,922 Medium & low-temp commercial refrigeration R-502, R-22 POE
R-407C HFC Blend (Zeotrope) 0 1,774 A/C & heat pumps (R-22 retrofit) R-22 POE
R-32 HFC (Pure) 0 675 Residential A/C (mini-splits), heat pumps R-410A (component) POE
R-438A (MO99) HFC Blend (Zeotrope) 0 2,265 R-22 drop-in retrofit, A/C & refrigeration R-22 Mineral / Alkylbenzene / POE
R-448A (Solstice N40) HFO/HFC Blend 0 1,273 Medium & low-temp commercial refrigeration R-404A, R-22 POE
R-449A (Opteon XP40) HFO/HFC Blend 0 1,282 Medium & low-temp commercial refrigeration R-404A, R-22 POE